| Ratd Voltage: | 10kv 11kv 12kv | Phase: | Single |
|---|---|---|---|
| Accuracy Class: | 0.5, 0.2S, 10P, 5P | Ambient Temperature: | -45℃ To +40℃ |
| Material: | Cast Resin | Standard: | IEC/GB |
| Installation Location: | Power Plants, Substations | Rated Insulation Level: | 12/42/75kV |
| Highlight: | 12kv CT Current Transformer,Cast Resin CT Current Transformer,LZZW-10 CT Current Transformer |
||
1. Technical data OF LZZW-10 Type 10kv 11kv 12kv Outdoor CT Current Transformer
1.rated insulation level: 12/42/75kV
2.rated frequency: 50/60Hz
3.burden power factor): COSØ=0.8 lagging
4.technical standard accords with):outdoor
5. technical standard according with:IEC60044-1:2003
2. Specification
| rated transformation ratio(A) |
Accuary classes combination |
rated output(VA) | (ALF) | (FS) | short-time thermal current Ith(kA/S) |
rated dynamic current Idyn(kA) |
||
| measuring | protective | |||||||
| 0.2(S) | 0.5 | 10p | ||||||
| 10-200/5 |
0.2(S)/0.2(S) 0.2(S)/0.5 0.2(S)/10P 0.5/10P 0.2S/0.5/10P 0.2/0.5/10P
|
10 15 |
15 | 15 |
10 15 20 |
5 (10) |
150 I1n | 375I1n |
| 300/5 | 31.5 | 80 | ||||||
| 400/5 | 31.5 | 80 | ||||||
| 500/5 | 40 | 100 | ||||||
| 600/5 | 50 | 125 | ||||||
| 800/5 | 20 | 63 | 125 | |||||
| 1000/5 | 80 | 160 | ||||||
| 1200-1500/5 | 80 | 160 | ||||||
Note: upon request we are glad to offer transformers according to other technical special.
3. Photo
4. Factory
![]()
5. Delivery
![]()
6. FAQ
1. Send the technical data, better for all useful information; we will make a good recommendation.
2. The lead time depend on quantity of order. Some standard type is on stock. Otherwise, it will take 3-15 days.
3. Usually shipped by sea, small order or urgent order we can send you by air.
4. All our activities are accredited to ISO 14001:2015 and IEC standard.
5. Technology ensure the quality satisfy international request.